DocumentCode :
1347708
Title :
Ampacity of diversely loaded cables in covered and uncovered trays
Author :
Black, W.Z. ; Harshe, Bruce L.
Author_Institution :
George W. Woodruff Sch. of Mech. Eng., Georgia Inst. of Technol., Atlanta, GA, USA
Volume :
15
Issue :
1
fYear :
2000
fDate :
1/1/2000 12:00:00 AM
Firstpage :
3
Lastpage :
7
Abstract :
The existing code for ampacity of cables in a tray does not account for load diversity among the cables and it does not consider the presence of tray covers. This paper provides two factors that can be used to determine ampacity values for these two cases. These factors can be used in conjunction with existing code ampacity values so that cable ampacities can be calculated for diversely loaded, covered and uncovered trays. Also, the case of a few heavily loaded cables in an otherwise lightly loaded tray is addressed. This particular situation can produce nonconservative ampacity values if treated with a one-dimensional heat transfer model. The problem of both load diversity, and the presence of a cover are addressed with a computer code that has been described in previous papers. The computer model is designed to provide conservative ampacity values by assuming that the more highly-loaded cables are placed along the tray centerline and the lightly-loaded cables are positioned on the outer surfaces of the cable bundle. In this way the heavily-loaded cables are insulated from the environment and thus the program calculates a conservative cable temperature. The factors that account for load diversity show that a small percentage of cables in the tray can be loaded significantly beyond the code allowable ampacity value if the remainder of the cables are lightly loaded or unenergized. On the other hand, the code-allowable ampacity must be reduced by up to 25% when a solid cover is placed over the tray
Keywords :
electric conduits; heat transfer; power cables; power engineering computing; cable ampacity; cable bundle; code ampacity values; computer code; computer model; conservative cable temperature; covered trays; diversely loaded cables ampacity; heavily loaded cables; lightly-loaded cables; load diversity; nonconservative ampacity values; one-dimensional heat transfer model; tray centerline; tray covers; uncovered trays; Cable insulation; Heat transfer; Mechanical engineering; Shape; Solids; Standards publication; Temperature; Thermal conductivity; Thermal factors; Thermal loading;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.847220
Filename :
847220
Link To Document :
بازگشت