DocumentCode
1347769
Title
Reducing dead time for single-phase auto-reclosing on a series-capacitor compensated transmission line
Author
Tran-Quoc, Tuan ; Hadj-Said, Nouredine ; Sabonnadière, Jean Claude ; Feuillet, René
Volume
15
Issue
1
fYear
2000
fDate
1/1/2000 12:00:00 AM
Firstpage
51
Lastpage
56
Abstract
This paper presents a single-phase auto-reclosing study of a 500 kV Vietnamese transmission line. The success of the single-phase auto-reclosing depends on the extinction of the secondary arc. Therefore, the influences of several factors such as shunt and neutral reactors, faulted phase and location, capacitive and inductive coupling and series capacitor discharge on the extinction of secondary arc are investigated. This paper presents the influence of single-phase auto-reclosing on the transient stability of the Vietnam system. A new method in order to reduce the dead time for single-phase auto-reclosing is proposed
Keywords
arcs (electric); power capacitors; power system transient stability; power transmission faults; power transmission lines; 500 kV; Vietnam; capacitive coupling; dead time reduction; fault location; faulted phase; inductive coupling; neutral reactors; secondary arc extinction; series capacitor discharge; series-capacitor compensated transmission line; shunt reactors; single-phase auto-reclosing; transient stability; Capacitors; Couplings; Fault location; Inductors; Power generation; Power system stability; Power system transients; Power transmission lines; Shunt (electrical); Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.847228
Filename
847228
Link To Document