• DocumentCode
    1347885
  • Title

    Factors that influence transformer no-load current harmonics

  • Author

    Al-Haj, Aiman Hassan ; El-Amin, Ibrahim

  • Author_Institution
    Saudi Transformers Co., Dammam, United Arab Emirates
  • Volume
    15
  • Issue
    1
  • fYear
    2000
  • fDate
    1/1/2000 12:00:00 AM
  • Firstpage
    163
  • Lastpage
    166
  • Abstract
    The harmonic components of the no-load current are influenced by many factors. These factors are the flux density, the degree of saturation and the core stacking technique. This paper tested many transformers for the no-load current and its harmonic components. A slight over-excitation results in a substantial increase of the THD level. The increase in the THD is not linear with the flux density. Also this work has demonstrated that having a lower no-load current should not be an indication of lower harmonics. The simulation of the transformer through the use of nonlinear inductors and resistors provided reasonable accuracy
  • Keywords
    harmonic distortion; harmonics; magnetic flux; power transformers; transformer cores; THD level increase; core stacking technique; flux density; harmonic components; lower harmonics; no-load current; nonlinear inductors; over-excitation; resistors; transformer no-load current harmonics; Circuit faults; Current measurement; Current transformers; IEC standards; Magnetic cores; Magnetic materials; Petroleum; Stacking; Testing; Transformer cores;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.847245
  • Filename
    847245