Title :
Design and implementation of AC voltage dependent current order limiter at Pacific HVDC Intertie
Author :
Bunch, Richard ; Kosterev, Dmitry
Author_Institution :
Transmissiobn Bus. Line, Bonneville Power Adm., Vancouver, WA, USA
fDate :
1/1/2000 12:00:00 AM
Abstract :
This paper presents design and implementation of AC-voltage dependent current order limiter at the Pacific WDC Intertie. Reactive power and inertial support to the Celilo HVDC terminal have been limited because of new operating requirements for hydropower plants on the lower Columbia River. Under these operating conditions, a large set of contingencies was identified when the PDCI can be contributing to AC voltage collapse in the lower Columbia area and to north-south power oscillations. On August 10, 1996, a WSCC system outage occurred under similar generating conditions. To correct the PDCI dynamic response, we designed and implemented the AC-VDCOL function in the PDCI pole controls. The system studies demonstrated consistent benefit of the new controls for the system stability and dynamic performance. The system tests confirmed AC-VDCOL benefit
Keywords :
HVDC power transmission; current limiters; dynamic response; power system dynamic stability; power system interconnection; power system transient stability; reactive power control; AC voltage collapse; AC voltage dependent current order limiter; Celilo HVDC terminal; Pacific HVDC Intertie; WSCC system outage; dynamic response correction; hydropower plant operating requirements; inertial support; lower Columbia River; north-south power oscillations; pole controls; reactive power; system stability; Control systems; Current control; HVDC transmission; Hydroelectric power generation; Inverters; Reactive power; Rectifiers; Stability; Thyristors; Voltage control;
Journal_Title :
Power Delivery, IEEE Transactions on