DocumentCode :
1348589
Title :
On Seismic Response of Substation Equipment and Application of Base Isolation to Transformers
Author :
Saadeghvaziri, M. Ala ; Feizi, B. ; Kempner, L., Jr. ; Alston, D.
Author_Institution :
Dept. of Civil Eng., New Jersey Inst. of Technol., Newark, NJ, USA
Volume :
25
Issue :
1
fYear :
2010
Firstpage :
177
Lastpage :
186
Abstract :
This paper presents seismic performance of electric substation transformers, and discusses advantages and considerations in the use of base isolation as a viable hazard mitigation option. Substation transformers and bushings are the most critical elements within the power delivery system and their performances during past earthquakes in the U.S. and abroad have not been satisfactory. Finite-element analyses indicate that the interaction between these two critical elements has a significant effect on seismic vulnerability of substations. In light of dynamic characteristics of this equipment, base isolation can be very effective in mitigating this adverse interaction. Furthermore, due to high-inertia reduction, base isolation can also have beneficial effects on the long-term longevity of transformers and on foundation performance during seismic events. Larger displacement demand and uplift, however, are issues that must be considered in the application of base isolation. Through an actual case study (433.3-MVA transformer in a high-voltage substation), a simplified model of the transformer bushing will be developed and the results of fixed base case and base isolated case are compared. Moreover, design concepts will be investigated that will demonstrate larger displacement can be accommodated; and that considering transformer geometry, peak ground acceleration, amount of inertia reduction, and isolator´s friction coefficient for this transformer uplift is not an issue.
Keywords :
bushings; earthquakes; power transformer insulation; power transformer protection; seismic waves; substation protection; base isolation; electric substation transformer; finite element analysis; hazard mitigation option; high inertia reduction; high voltage substation; substation equipment seismic response; transformer bushing; Base isolation; bushings; power substations; seismic response; transformers;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2009.2033971
Filename :
5345686
Link To Document :
بازگشت