Title :
Temporary Overvoltage and GPR Characteristics of Distribution Feeders With Multigrounded Neutral
Author :
Acharya, Janak R. ; Wang, Yunfei ; Xu, Wilsun
Author_Institution :
Dept. of Electr. & Comput. Eng., Univ. of Alberta, Edmonton, AB, Canada
fDate :
4/1/2010 12:00:00 AM
Abstract :
Three-phase four-wire multigrounded neutral (MGN) is the preferred distribution line configuration in North America. Its performance characteristics, such as temporary overvoltage (voltage swell) and ground potential rise (GPR), are difficult to understand and assess due to the presence of a neutral conductor and the conductor´s multiple grounding nature. The characteristics are further affected by unique parameters, such as grounding intervals and the coupling between neutral and phase conductors. This paper conducts analytical studies on the phenomena of temporary overvoltage and GPR associated with MGN configurations. The purpose is to reveal the mechanisms leading to the phenomena and their contributing factors. Approximate formulae are derived to quantify the impact of various factors. The findings are confirmed by the simulation results.
Keywords :
distribution networks; earthing; overvoltage protection; GPR characteristics; North America; distribution feeders; distribution line configuration; ground potential rise; multigrounded neutral distribution feeders; neutral conductor; phase conductors; temporary overvoltage; Ground potential rise; grounding; multigrounded neutral; temporary overvoltage;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.2009.2034456