DocumentCode :
13490
Title :
A new fuzzy logic approach for consistent interpretation of dissolved gas-in-oil analysis
Author :
Abu-Siada, A. ; Hmood, S. ; Islam, Shariful
Author_Institution :
Curtin Univ., Perth, WA, Australia
Volume :
20
Issue :
6
fYear :
2013
fDate :
Dec-13
Firstpage :
2343
Lastpage :
2349
Abstract :
Dissolved gas analysis (DGA) of transformer oil is one of the most effective power transformer condition monitoring tools. There are many interpretation techniques for DGA results however all these techniques rely on personnel experience more than analytical formulation. As a result, various interpretation techniques do not necessarily lead to the same conclusion for the same oil sample. Furthermore, significant number of DGA results fall outside the proposed codes of the current based-ratio interpretation techniques and cannot be diagnosed by these methods. Moreover, ratio methods fail to diagnose multiple fault conditions due to the mixing up of produced gases. To overcome these limitations, this paper introduces a new fuzzy logic approach to reduce dependency on expert personnel and to aid in standardizing DGA interpretation techniques. The approach relies on incorporating all existing DGA interpretation techniques into one expert model. DGA results of 2000 oil samples that were collected from different transformers of different rating and different life span are used to establish the model. Traditional DGA interpretation techniques are used to analyze the collected DGA results to evaluate the consistency and accuracy of each interpretation technique. Results of this analysis were then used to develop the proposed fuzzy logic model.
Keywords :
chemical analysis; condition monitoring; fault diagnosis; fuzzy logic; power transformers; transformer oil; DGA interpretation techniques; dissolved gas in oil analysis; fuzzy logic approach; power transformer condition monitoring tools; ratio methods; transformer oil; Discharges (electric); Fault diagnosis; Fuzzy logic; Gases; Mathematical model; Oil insulation; Power transformers; DGA; Transformer diagnosis; condition monitoring; fuzzy logic;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2013.6678888
Filename :
6678888
Link To Document :
بازگشت