DocumentCode
1351142
Title
Detection of Symmetrical Faults by Distance Relays During Power Swings
Author
Lotfifard, Saeed ; Faiz, Jawad ; Kezunovic, Mladen
Author_Institution
Dept. of Electr. & Comput. Eng., Texas A&M Univ., College Station, TX, USA
Volume
25
Issue
1
fYear
2010
Firstpage
81
Lastpage
87
Abstract
For maintaining security of distance relays, power swing blocking is necessary to prevent unintended operation under power swings. To be dependable, distance relays must operate whenever a fault occurs. Therefore, detecting faults during power swings is an important issue since the relay should be able to differentiate the fault condition and not be blocked during that time. This paper presents a new method for detecting a symmetrical fault during a power swing, based on extracting components of the current waveform using the Prony method. The merit of the method is demonstrated by simulating different faults during power swing conditions using the Alternate Transients Program version of the Electromagnetic Transients Program.
Keywords
fault diagnosis; relay protection; Prony method; alternate transients program; current waveform; distance relays security; electromagnetic transients program; fault condition; fault detection; power swing blocking; symmetrical faults detection; Distance relay; power swing; prony method; symmetrical fault;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2009.2035224
Filename
5350416
Link To Document