DocumentCode :
1351142
Title :
Detection of Symmetrical Faults by Distance Relays During Power Swings
Author :
Lotfifard, Saeed ; Faiz, Jawad ; Kezunovic, Mladen
Author_Institution :
Dept. of Electr. & Comput. Eng., Texas A&M Univ., College Station, TX, USA
Volume :
25
Issue :
1
fYear :
2010
Firstpage :
81
Lastpage :
87
Abstract :
For maintaining security of distance relays, power swing blocking is necessary to prevent unintended operation under power swings. To be dependable, distance relays must operate whenever a fault occurs. Therefore, detecting faults during power swings is an important issue since the relay should be able to differentiate the fault condition and not be blocked during that time. This paper presents a new method for detecting a symmetrical fault during a power swing, based on extracting components of the current waveform using the Prony method. The merit of the method is demonstrated by simulating different faults during power swing conditions using the Alternate Transients Program version of the Electromagnetic Transients Program.
Keywords :
fault diagnosis; relay protection; Prony method; alternate transients program; current waveform; distance relays security; electromagnetic transients program; fault condition; fault detection; power swing blocking; symmetrical faults detection; Distance relay; power swing; prony method; symmetrical fault;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2009.2035224
Filename :
5350416
Link To Document :
بازگشت