DocumentCode :
1351148
Title :
Current Interruption in Low-Voltage Circuit Breakers
Author :
Balestrero, Andrea ; Ghezzi, Luca ; Popov, Marjan ; Van der Sluis, Lou
Author_Institution :
ABB S.p.A., Bergamo, Italy
Volume :
25
Issue :
1
fYear :
2010
Firstpage :
206
Lastpage :
211
Abstract :
Low-voltage current interruption is studied in this paper in order to develop a suitable blackbox model for low-voltage circuit breakers. The electric arc will be modeled by means of electrical quantities. Accurate post-arc current measurements by a high sensitivity current probe and signal analysis techniques (Savitsky-Golay filtering) are adopted to extract information. A set of interrupting performance evaluators is proposed, and the best performing indicators are selected. Theoretical explanations provide insight in the physical processes of low-voltage interruption. The difference with the classical context of blackbox modeling in medium- and high-voltage circuit breakers is explained, based on the different relative weight of the arc voltage and voltage supply.
Keywords :
arcs (electric); circuit breakers; electric current measurement; arc voltage; blackbox model; current interruption; electric arc; high sensitivity current probe; low-voltage circuit breakers; low-voltage current interruption; medium-voltage circuit breakers; post-arc current measurements; signal analysis techniques; voltage supply; Blackbox models; Savitsky–Golay filter; interruption performance evaluators; low-voltage arc;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2009.2035298
Filename :
5350418
Link To Document :
بازگشت