DocumentCode
135299
Title
Applying process immunity time to assess annual industrial process trips
Author
Cebrian, Juan C. ; Kagan, Nelson ; Milanovic, Jovica V.
Author_Institution
Polytech. Sch., Univ. of Sao Paulo, Sao Paulo, Brazil
fYear
2014
fDate
27-31 July 2014
Firstpage
1
Lastpage
5
Abstract
The effect of voltage sag to customer´s process has been studied by different authors. They propose methods in order to assess annual indices related to process trip due to sags and long duration interruptions (LDI). However, these methods don´t consider the process immunity time (PIT) during the estimation of these indices. This paper introduces a procedure where PIT is included in order to increase the accuracy of annual indices. The procedure is applied to a representative distribution network. The results show that (i) the difference, between the values obtained considering PIT or not, is approx. on average 50% and (ii) only 6% the total of event between sag and LDI affects the customer´s process.
Keywords
distribution networks; power supply quality; LDI; PIT; annual industrial process trips; customer process; distribution network; index estimation; long-duration interruption; process immunity time; voltage sag effect; Educational institutions; Power quality; Process control; Sensitivity; Uncertainty; Variable speed drives; Voltage fluctuations; power quality; process immunity time; reliability; voltage sags;
fLanguage
English
Publisher
ieee
Conference_Titel
PES General Meeting | Conference & Exposition, 2014 IEEE
Conference_Location
National Harbor, MD
Type
conf
DOI
10.1109/PESGM.2014.6939243
Filename
6939243
Link To Document