• DocumentCode
    135660
  • Title

    Research on Voltage Stability Region tangent plane of power system with Doubly-Fed Induction Generator wind farm

  • Author

    Zeyu Qin ; Rui Ma

  • Author_Institution
    Dept. of Electr. & Inf., Changsha Univ. of Sci. & Technol., Changsha, China
  • fYear
    2014
  • fDate
    27-31 July 2014
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    This paper presents a tangent plane math model of Voltage Stability Region in Power Injection Space (IVSR) considering Doubly-Fed Induction Generator (DFIG) wind farm penetration. In order to calculate these tangent plane equations of IVSR, a novel math model of DFIG is added into the power flow equations, which considers the steady state parameters of wind turbine. And then the tangent planes are constructed, which constitute the approximate boundary of IVSR. Moreover, the load parameters and sensitivities of tangent planes are calculated with different wind speed so as to analyze the change of IVSR boundary which consists of tangent planes. Finally, the conclusion can be drawn that the range and the shape of the boundary of IVSR will be changed when the wind speed is varying.
  • Keywords
    asynchronous generators; load flow; power system stability; wind power plants; wind turbines; doubly-fed induction generator; power flow equations; power injection space; power system stability; tangent plane; voltage stability region; wind farm; wind turbine; Generators; Mathematical model; Power system stability; Wind farms; Wind power generation; Wind speed; doubly-fed induction generator; tangent plane; voltage stability region; wind farm;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    PES General Meeting | Conference & Exposition, 2014 IEEE
  • Conference_Location
    National Harbor, MD
  • Type

    conf

  • DOI
    10.1109/PESGM.2014.6939513
  • Filename
    6939513