    Harmonic voltages and currents in Y- and delta-connected transformers

  • Author

    Clinker, R.C.

  • Volume
    33
  • Issue
    5
  • fYear
    1914
  • fDate
    5/1/1914 12:00:00 AM
  • Firstpage
    785
  • Lastpage
    789
  • Abstract
    The paper reviews the conditions under which triple harmonic voltages and currents are produced in Y-and delta-connected transformers. These voltages are produced by hysteresis in the core. In a single-phase transformer, increase of series resistance tends to suppress the current harmonic and produce the voltage harmonic. In three-phase transformers, a Y connection suppresses the current harmonic and allows the full flux and voltage harmonics to appear. Delta connection provides a closed path for the current harmonic, and suppresses the triple voltage. A case is cited where a Y-connected auto-transformer was used to step up from 6600 to 12,000 volts at a substation. The neutral was not grounded, and trouble resulted due to partial resonance at triple frequency between line capacity and transformer reactance. The paper shows that, although not generally recognized, a triple component can exist in the line-to-line e.m.f. wave of a three-phase system. This is possible in a case where a two-to-three-phase transformation is used, and when the e.m.f. wave of the two-phase generator contains a triple harmonic. Vector diagrams and curves are given illustrating this possible effect.
  • Keywords
    Generators; Harmonic analysis; Phase transformers; Power transformer insulation; Resistance; Vectors; Windings;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Proceedings of the
  • Publisher
    ieee
  • ISSN
    0097-2444
  • Type

    jour

  • DOI
    10.1109/PAIEE.1914.6660861
  • Filename
    6660861