DocumentCode
1358697
Title
Stand alone intelligent digital distance relay
Author
Li, K.K. ; Lai, L.L. ; David, A.K.
Author_Institution
Hong Kong Polytech. Univ., China
Volume
15
Issue
1
fYear
2000
fDate
2/1/2000 12:00:00 AM
Firstpage
137
Lastpage
142
Abstract
Remote end infeed causes problems in distance relay especially under high resistance earth fault conditions. Although a distance relay set to an ideal operating region can cover the fault resistance at one particular load condition, the operating region is affected by changes in load condition. Hence a distance relay may overreach or underreach when load changes. From the main factors which affect the ideal digital distance relay operating region, a stand alone intelligent digital distance relay which can adapt to these changes is presented. This approach does not need communication links from the remote end of the line or the system control center. Numerous computer simulations have been carried out on realistic system configurations and the results show that there is a high potential for developing an intelligent digital distance relay
Keywords
neural nets; power engineering computing; power system faults; power system protection; relay protection; adaptive digital relaying; artificial intelligence; computer simulations; distance relay overreach; distance relay underreach; fault resistance; high resistance earth fault conditions; ideal operating region; intelligent digital distance relay; neural networks; remote end infeed; stand alone intelligent digital distance relay; system control center; Artificial intelligence; Circuit faults; Digital relays; Impedance; Integrated circuit interconnections; Power system interconnection; Power system relaying; Power system simulation; Protection; Protective relaying;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/59.852112
Filename
852112
Link To Document