A Two Terminal Network-Based Method for Discrimination Between Internal Faults and Inrush Currents
Author
Ma, Jing ; Wang, Zengping ; Yang, Qixun ; Liu, Yilu
Author_Institution
Sch. of Electr. & Electron. Eng., North China Electr. Power Univ., Beijing, China
Volume
25
Issue
3
fYear
2010
fDate
7/1/2010 12:00:00 AM
Firstpage
1599
Lastpage
1605
Abstract
A novel scheme based on two-terminal network to distinguish the inrush current from the internal fault current in the power transformer is proposed. By eliminating the mutual flux linkage in the transformer loop equation, a two-terminal network containing only the winding resistance and the leakage inductance is generated. According to the absolute difference of active power (ADOAP) flowing into and consumed by the two-terminal network, the criterion to identify the internal fault is developed. A total of 162 experimental cases have been tested and the proposed method is able to reliably and accurately discriminate internal faults from inrush currents with easy implementation.
Keywords
fault currents; power transformers; absolute difference of active power; inrush currents; internal fault current; mutual flux linkage elimination; power transformer; transformer loop equation; two terminal network-based method; Inrush current; internal fault; power transformer; two-terminal network;