Title :
Harmonic Impact on Distribution Transformer No-Load Loss
Author :
Kefalas, Themistoklis D. ; Kladas, Antonios G.
Author_Institution :
Sch. of Electr. & Comput. Eng., Nat. Tech. Univ. of Athens, Athens, Greece
Abstract :
The losses in European Union distribution transformers are estimated at about 33 TW ??h/year, whereas reactive power and harmonic losses add a further 5 TW ??h/year. The reduction of distribution transformer no-load loss is particularly important as the ratio of no-load to load losses is nearly three. In this paper, the no-load operation of wound-core transformers under sinusoidal and distorted supply-voltage conditions is investigated. For that purpose, a 2-D nonlinear transient finite-element analysis taking into account hysteresis has been developed. The hysteresis model is based on a modified Jiles-Atherton representation, and the proposed analysis is compared to experimental data.
Keywords :
finite element analysis; power transformers; 2-D nonlinear transient finite-element analysis; European Union distribution transformers; Jiles-Atherton representation; distribution transformer no-load loss; harmonic impact; power 5 TW; wound-core transformers; Finite element methods; industrial power system harmonics; magnetic anisotropy; magnetic cores; magnetic hysteresis; magnetic losses; nonlinear magnetics; power transformers; soft magnetic materials; transient analysis;
Journal_Title :
Industrial Electronics, IEEE Transactions on
DOI :
10.1109/TIE.2009.2030207