DocumentCode
1361074
Title
Digital fault location for parallel double-circuit multi-terminal transmission lines
Author
Funabashi, Toshihisa ; Otoguro, Hitomi ; Mizuma, Yoshishige ; Dube, Laurent ; Ametani, Akihiro
Author_Institution
Meidensha Corp., Tokyo, Japan
Volume
15
Issue
2
fYear
2000
fDate
4/1/2000 12:00:00 AM
Firstpage
531
Lastpage
537
Abstract
Two new methods are proposed for fault point location in parallel double-circuit multi-terminal transmission lines by using voltages and currents information from CCVTs and CTs at all terminal. These algorithms take advantage of the fact that the sum of currents flowing into a fault section equals the sum of the currents at all terminals. Algorithm 1 employs an impedance calculation and algorithm 2 employs the current diversion ratio method. Computer simulations are carried out and applications of the proposed methods are discussed. Both algorithms can be applied to all types of fault such as phase-to-ground and phase-to-phase faults. As one equation can be used for all types of fault, classification of fault types and selection of faulted phase are not required. Phase components of the line impedance are used directly, so compensation of unbalanced line impedance is not required
Keywords
fault location; power system analysis computing; power transmission faults; power transmission lines; algorithms; computer simulation; current diversion ratio method; digital fault location; fault point location; fault section currents; impedance calculation; parallel double-circuit multi-terminal transmission lines; phase-to-ground faults; phase-to-phase faults; Application software; Circuit faults; Computer simulation; Distributed parameter circuits; Equations; Fault location; Impedance; Transmission line measurements; Transmission lines; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.852980
Filename
852980
Link To Document