DocumentCode
1361117
Title
Comparison of performance indices for detection of proximity to voltage collapse
Author
Cañizares, Claudio A. ; De Souz, Antonio C Z ; Quintana, Victor H.
Author_Institution
Dept. of Electr. & Comput. Eng., Waterloo Univ., Ont., Canada
Volume
11
Issue
3
fYear
1996
fDate
8/1/1996 12:00:00 AM
Firstpage
1441
Lastpage
1450
Abstract
The paper proposes a new test function to be used in an existent performance index for detection of proximity to a static voltage collapse point. This test function is based on a reduction of the load flow Jacobian with respect to the critical bus of a system. The test function is compared with known singular values and eigenvalues indices, and with other previously proposed test functions. A thorough analysis of the similarities, advantages, and disadvantages of all these indices and test functions is presented. The techniques are tested and compared on the IEEE 300 bus test system, showing the effect of system characteristics and limits in these indices and functions
Keywords
Jacobian matrices; eigenvalues and eigenfunctions; load flow; performance index; power system stability; IEEE 300 bus test system; eigenvalues indices; load flow Jacobian; performance index; performance indices; singular values; static voltage collapse proximity; test function; Bifurcation; Eigenvalues and eigenfunctions; Equations; Jacobian matrices; Load flow analysis; Power system modeling; Power system planning; Student members; System testing; Voltage;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/59.535685
Filename
535685
Link To Document