• DocumentCode
    1361117
  • Title

    Comparison of performance indices for detection of proximity to voltage collapse

  • Author

    Cañizares, Claudio A. ; De Souz, Antonio C Z ; Quintana, Victor H.

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Waterloo Univ., Ont., Canada
  • Volume
    11
  • Issue
    3
  • fYear
    1996
  • fDate
    8/1/1996 12:00:00 AM
  • Firstpage
    1441
  • Lastpage
    1450
  • Abstract
    The paper proposes a new test function to be used in an existent performance index for detection of proximity to a static voltage collapse point. This test function is based on a reduction of the load flow Jacobian with respect to the critical bus of a system. The test function is compared with known singular values and eigenvalues indices, and with other previously proposed test functions. A thorough analysis of the similarities, advantages, and disadvantages of all these indices and test functions is presented. The techniques are tested and compared on the IEEE 300 bus test system, showing the effect of system characteristics and limits in these indices and functions
  • Keywords
    Jacobian matrices; eigenvalues and eigenfunctions; load flow; performance index; power system stability; IEEE 300 bus test system; eigenvalues indices; load flow Jacobian; performance index; performance indices; singular values; static voltage collapse proximity; test function; Bifurcation; Eigenvalues and eigenfunctions; Equations; Jacobian matrices; Load flow analysis; Power system modeling; Power system planning; Student members; System testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/59.535685
  • Filename