DocumentCode :
1361194
Title :
A modified back-to-back HVDC system for 36-pulse operation
Author :
Villablanca, Miguel ; Valle, Julio Del ; Rojas, Julio ; Abarca, Jose ; Rojas, Wilson
Author_Institution :
Dept. of Electr. Eng., Santiago Univ. of Chile, Chile
Volume :
15
Issue :
2
fYear :
2000
fDate :
4/1/2000 12:00:00 AM
Firstpage :
641
Lastpage :
645
Abstract :
Recently, back-to-back HVDC power transmission systems have greatly increased. They interconnect large power systems offering numerous technical and economic benefits. The design of AC system filters, however, is not an easy task. Also, filters do not remove all the harmonics for which they are tuned, are costly and have a complicated transient behavior. In this paper a 36-pulse filterless configuration for back-to-back HVDC systems is proposed, whereby harmonics are eliminated within the converter, thus opening the possibility of advantages in aspects of design, reliability and capital savings
Keywords :
HVDC power convertors; HVDC power transmission; harmonic distortion; harmonics suppression; power conversion harmonics; power system interconnection; 36-pulse operation; HVDC power convertor harmonics elimination; economic benefits; large power systems interconnection; modified back-to-back HVDC transmission system; technical benefits; transient behavior; Active filters; Bridge circuits; HVDC transmission; Inverters; Load flow; Power harmonic filters; Power system harmonics; Power system interconnection; Power system transients; Rectifiers;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.852998
Filename :
852998
Link To Document :
بازگشت