Observation and analysis of lightning surges at substations connected with UHV designed transmission lines
Author
Yamada, Takeshi ; Narita, Tomomi ; Shioda, Toru ; Okabe, Shigemitsu ; Zaima, Eiichi
Author_Institution
Tokyo Electr. Power Co. Inc., Yokohama, Japan
Volume
15
Issue
2
fYear
2000
fDate
4/1/2000 12:00:00 AM
Firstpage
675
Lastpage
683
Abstract
On UHV-class transmission lines with sections of 500 kV class insulation, lightning observations have been made to study the generation and the propagation of overvoltage into substations. Voltages and currents were recorded at substations and at junction-tower footings during three flashovers on the UHV system. These observations were then matched to EMTP calculations by adjusting the average soil resistivity and the average conductor height in the propagation model. It is also found that the attenuation due to corona of voltages was small because it is expected to be minimal for 8-conductor bundles
Keywords
EMTP; electrical resistivity; flashover; lightning; overvoltage; poles and towers; power overhead lines; soil; substations; surges; 500 kV; EMTP calculations; UHV transmission lines; conductor height; corona; flashovers; insulation; junction-tower footings; lightning surges analysis; lightning surges observation; overvoltage generation; overvoltage propagation; shielding failure; soil resistivity; substations; voltages attenuation; EMTP; Flashover; Insulation; Lightning; Optical propagation; Soil; Substations; Surges; Transmission lines; Voltage control;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.853004
Filename
853004
Link To Document