Title :
Evaluation of transmission line arresters against winter lightning
Author :
Wakai, Takeo ; Itamoto, Naoki ; Sakai, Tutomu ; Ishii, Masaru
Author_Institution :
Hokuriku Electr. Power Co., Toyama, Japan
fDate :
4/1/2000 12:00:00 AM
Abstract :
The authors have tested 154 kV class transmission line arresters by installing them on an instrumented tower of a double-circuit test transmission line during winter seasons since 1993. The tower is struck by natural and artificially-triggered lightning several times during each winter season. The conventional transmission line arrester designed against summer lightning was effective against winter lightning. The authors developed a new transmission line arrester of reduced rating, and investigated its applicability against winter lightning based on EMTP analysis, taking account of measured lightning current waveforms in winter. Although omission of an earth wire is not feasible on transmission towers having high footing resistance, the new arrester of reduced rating is a reasonable option to realize a line of high lightning performance
Keywords :
EMTP; arresters; lightning protection; poles and towers; power transmission lines; power transmission protection; 154 kV; EMTP analysis; artificially-triggered lightning; double-circuit test transmission line; high footing resistance; tower; transmission line arresters; winter lightning; winter seasons; Arresters; Current measurement; EMTP; Electrical resistance measurement; Instruments; Lightning; Poles and towers; Testing; Transmission line measurements; Transmission lines;
Journal_Title :