• DocumentCode
    1364052
  • Title

    What we must learn from 1995 the Great Kobe-Earthquake. Considerations on the distribution power poles

  • Author

    Kobayashi, Miki

  • Author_Institution
    Kogakuin Univ., Tokyo, Japan
  • Volume
    12
  • Issue
    3
  • fYear
    1997
  • fDate
    7/1/1997 12:00:00 AM
  • Firstpage
    1368
  • Lastpage
    1373
  • Abstract
    The Great Kobe Earthquake destroyed numerous electric power facilities. Officials estimated the minimum total cost of the damage from this earthquake to be Y230 billion (US $2.3 billion). The quake halted the power supply to over one million users for 9,000 minutes. This long blackout resulted from heavy destruction to the distribution system, as the heavy shock of the quake forced numerous power poles to incline, sending line conductors to the ground below. Fortunately, safety systems adequately protected main facilities like electric power stations and substations from serious damage. Field observations focused on two areas: (1) location of heavy equipment on the power poles; and (2) reinforcement of the power poles after the quake. The results of this survey indicate that preventive adjustments and reinforcements are urgently needed to protect such power poles against future earthquakes
  • Keywords
    disasters; distribution networks; earthquakes; poles and towers; power overhead lines; Great Kobe Earthquake; distribution power poles; electric power facilities; power supply blackout; reinforcement; safety systems; Cities and towns; Concrete; Conductors; Earthquakes; Electric shock; Electrical safety; Partial response channels; Power system protection; Steel; Substation protection;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.637016
  • Filename
    637016