Title :
Research on on-line insulation monitoring and fault location method of mine power supply XLPE cable
Author :
Xudong Wang ; Tao Xia
Author_Institution :
Henan Polytech. Univ., Jiao Zuo, China
fDate :
Aug. 31 2014-Sept. 3 2014
Abstract :
Due to the dust, humidity and many other causes, the mine cable insulation will decrease gradually. This would cause leakage accidents and cable single-phase ground fault and then endanger the safety of the coal mines and workers. In order to solve above problems, this paper proposed a coal mine on-line insulation monitoring and fault location method. The way to achieve the goal is by superimposing a different frequency signal (DFS). When the operation of the cable is normal, it will monitoring the insulation condition of mine cable on-line, and when a single-phase ground fault occurs it will convert to locate the point of fault automatically. It combines the insulation monitoring and fault location in one system. The ATP/MATLAB simulation results show the feasibility and effectiveness of the method.
Keywords :
XLPE insulation; coal; fault location; leakage currents; power cable insulation; ATP-MATLAB simulation; DFS; XLPE cable; cable single-phase ground fault; coal mines; different frequency signal; fault location; leakage accidents; mine cable insulation; mine power supply; on-line insulation monitoring; Cable insulation; Fault location; Fuel processing industries; Monitoring; Power cables; Resistance;
Conference_Titel :
Transportation Electrification Asia-Pacific (ITEC Asia-Pacific), 2014 IEEE Conference and Expo
Conference_Location :
Beijing
Print_ISBN :
978-1-4799-4240-4
DOI :
10.1109/ITEC-AP.2014.6940919