    SF6 breakdown in GIS

  • Author

    Tekletsadik, K. ; Campbell, L.C.

  • Author_Institution
    Dept. of Electron. & Electr. Eng., Strathclyde Univ., Glasgow, UK
  • Volume
    143
  • Issue
    5
  • fYear
    1996
  • fDate
    9/1/1996 12:00:00 AM
  • Firstpage
    270
  • Lastpage
    276
  • Abstract
    SF6 gas breakdown and spacer surface flashover volt-time characteristic curves were established for a GIS of D/d=55/25 (15 mm gap) and D/d=45/25 (10 mm gap) for 1.2/50, 0.5/50, 0.2/50 and osc/50 (1.64 MHz) μs impulse and disconnector induced VFT voltages. VFT volt-time curves established using actual breakdown voltages against actual time to breakdown were found to give a better representation of the dielectric performance, and thus are recommended for future applications. Highly inhomogeneous field geometries, such as particle contaminated gaps, caused downward turning of the v-t curves during VFT breakdowns at short times to breakdown
  • Keywords
    SF6 insulation; electric breakdown; electric strength; flashover; gas insulated substations; substation insulation; transients; 1.64 MHz; 10 mm; 15 mm; SF6; disconnector induced VFT voltages; electrode effects; fast transient voltages; gas breakdown; gas insulated substations; highly inhomogeneous field geometries; impulse voltages; particle contaminated gaps; spacer surface flashover; volt-time characteristic curves;
  • fLanguage
    English
  • Journal_Title
    Science, Measurement and Technology, IEE Proceedings -
  • Publisher
    iet
  • ISSN
    1350-2344
  • Type

    jour

  • DOI
    10.1049/ip-smt:19960546
  • Filename