DocumentCode :
1367729
Title :
An Approach Based on Analytical Expressions for Optimal Location of Voltage Sags Monitors
Author :
Espinosa-Juárez, Elisa ; Hernández, Araceli ; Olguin, Gabriel
Author_Institution :
Electr. Eng. Fac., Univ. Michoacana de San Nicolas de Hidalgo, Morelia, Mexico
Volume :
24
Issue :
4
fYear :
2009
Firstpage :
2034
Lastpage :
2042
Abstract :
This paper addresses the problem of identifying the optimal location for voltage sags monitors. The proposed approach is based on using a monitor reach matrix obtained from the solution of analytical expressions which are valid for any location of faults in the power system. This method provides the optimal number of monitoring devices and the best positions to place them in order to guarantee the observability of the whole system considering any type of fault (balanced or unbalanced). That is, the location of monitors obtained by means of the proposed algorithm ensures that any event leading to a voltage sag is captured by, at least, one voltage sag monitor. Several examples are provided showing the performance of the proposed formulation compared to other approaches.
Keywords :
fault location; matrix algebra; power supply quality; power system faults; power system measurement; analytical expressions; monitor reach matrix; optimal fault location; power system fault; voltage sag monitor; Condition monitoring; Frequency estimation; Observability; Power generation economics; Power quality; Power system analysis computing; Power system faults; Stochastic processes; System performance; Voltage fluctuations; Power quality (PQ); Power system; power quality monitoring; voltage sags (dips);
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2009.2028777
Filename :
5235726
Link To Document :