• DocumentCode
    1368353
  • Title

    Harmonic mitigator based on 12-pulse ac-dc converter for switched mode power supply

  • Author

    Kalpana, R. ; Bhuvaneswari, G. ; Singh, Bawa ; Singh, Sushil

  • Author_Institution
    Dept. of Electr. Eng., Indian Inst. of Technol., New Delhi, India
  • Volume
    3
  • Issue
    6
  • fYear
    2010
  • Firstpage
    947
  • Lastpage
    964
  • Abstract
    A novel harmonic mitigator based on the 12-pulse ac-dc converter, which is capable of suppressing up to 11th harmonics, is presented with reduced magnetic rating and low total harmonic distortion (THD) of ac mains current. A set of power quality indices on input ac mains and magnetic ratings for various autoconnected transformer configurations for the 12-pulse converter feeding a low voltage, high current and 12-kW switched mode power supply is also presented so that the best autoconnected transformer configuration can be chosen according to the requirements for this application. A laboratory prototype of the proposed ac-dc converter is developed and the test results are presented to validate the design and model of the converter system.
  • Keywords
    AC-DC power convertors; harmonic distortion; harmonics suppression; power transformers; switched mode power supplies; 12-pulse AC-DC converter; autoconnected transformer; converter system; harmonic mitigator; harmonic suppression; magnetic ratings; power 12 kW; switched mode power supply; total harmonic distortion;
  • fLanguage
    English
  • Journal_Title
    Power Electronics, IET
  • Publisher
    iet
  • ISSN
    1755-4535
  • Type

    jour

  • DOI
    10.1049/iet-pel.2009.0325
  • Filename
    5618883