• DocumentCode
    1369216
  • Title

    High-Performance Harmonic Isolation and Load Voltage Regulation of the Three-Phase Series Active Filter Utilizing the Waveform Reconstruction Method

  • Author

    Senturk, Osman S. ; Hava, Ahmet M.

  • Author_Institution
    Dept. of Electr. & Electron. Eng., Middle East Tech. Univ., Ankara, Turkey
  • Volume
    45
  • Issue
    6
  • fYear
    2009
  • Firstpage
    2030
  • Lastpage
    2038
  • Abstract
    This paper develops a waveform reconstruction method (WRM) for high accuracy and bandwidth signal decomposition of voltage-harmonic-type three-phase diode rectifier load voltage into its harmonic and fundamental components, which are utilized in the series active filter (SAF) control algorithms. The SAF-compensated system utilizing WRM provides high-performance load harmonic voltage isolation and load voltage regulation at steady-state and during transients compared to the system utilizing the synchronous reference-frame-based signal decomposition. In addition, reducing the line current sampling delay in the discrete-time implementation enhances the stability of the SAF. The simulations and experimental studies of a 10-kW three-phase SAF-compensated system prove the theory.
  • Keywords
    active filters; power harmonic filters; rectifying circuits; voltage control; waveform analysis; SAF control algorithm; bandwidth signal decomposition; harmonic isolation; load voltage regulation; power 10 kW; three-phase series active filter; voltage-harmonic-type three-phase diode rectifier; waveform reconstruction method; Harmonic; harmonic extraction; isolation; power quality; rectifier; series active filter (SAF); voltage regulation;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.2009.2031788
  • Filename