Harmonic response tests on distribution circuit potential transformers
Author
Cox, M.D. ; Berry, F.C. ; Govindarajan, S.N.
Author_Institution
Dept. of Electr. Eng., Louisiana Tech. Univ., Ruston, LA, USA
Volume
6
Issue
3
fYear
1991
fDate
7/1/1991 12:00:00 AM
Firstpage
973
Lastpage
978
Abstract
Experimental data are presented that show the performances of distribution circuit potential transformers operating with nonsinusoidal waveforms. Four standard magnetic voltage transformers designed for 60 Hz power applications and rated from 7.2 kV to 20 kV were tested. Ratio correction factor and phase angle measurements were conducted at rated 60 Hz voltage with harmonic distortion levels at and below 8%. Test results indicate that potential transformers rated up to 20 kV experience errors of less than 5% at harmonic frequencies up to 3500 Hz when operating into typical induction watthour meter burdens. The phase angle response is essentially linear over the frequency range used to test the transformers, with a typical phase angle of about -10° at frequencies of approximately 3 to 3.5 kHz
Keywords
distribution networks; harmonics; potential transformers; transformer testing; 60 Hz; 7.2 to 20 kV; distribution circuit potential transformers; harmonic distortion levels; harmonic response tests; nonsinusoidal waveforms; phase angle measurements; ratio correction factor; Circuit testing; Distortion measurement; Frequency; Harmonic distortion; Instrument transformers; Phase measurement; Power system harmonics; Probes; Voltage transformers; Watthour meters;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.85836
Filename
85836
Link To Document