• DocumentCode
    1370167
  • Title

    Fault current distribution in HV cable systems

  • Author

    Viel, E. ; Griffiths, H.

  • Author_Institution
    Sch. of Eng., Cardiff Univ., UK
  • Volume
    147
  • Issue
    4
  • fYear
    2000
  • fDate
    7/1/2000 12:00:00 AM
  • Firstpage
    231
  • Lastpage
    238
  • Abstract
    An advanced analytical model is presented for the evaluation of ground return currents at substations fed by both three and single-core cable circuits. The circuit model includes the accurate treatment of an intermediate substation between the source and the faulted substation, unlike Engineering Recommendation EA S.34, which adopts a more simplified approach. Through detailed parametric studies, the differences between the simplified and the more accurate treatment are quantified. The effects that variations in the key parameters-cable length and type, substation earth impedances have on the magnitude of the ground return current are identified and explained
  • Keywords
    current distribution; earthing; fault currents; power cables; power system faults; substations; HV power cable systems; analytical model; earth impedance; fault current distribution; ground return current; ground return currents; single-core cable circuits; substations; three-core cable circuits;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings-
  • Publisher
    iet
  • ISSN
    1350-2360
  • Type

    jour

  • DOI
    10.1049/ip-gtd:20000404
  • Filename
    859355