• DocumentCode
    1371012
  • Title

    Voltage sags: their impact on the utility and industrial customers

  • Author

    Melhorn, Christopher J. ; Davis, Timothy D. ; Beam, George E.

  • Author_Institution
    Electrotek Concepts Inc., Knoxville, TN, USA
  • Volume
    34
  • Issue
    3
  • fYear
    1998
  • Firstpage
    549
  • Lastpage
    558
  • Abstract
    This paper describes the impact of voltage sags on the electric utility and industrial customers. Several utility measures are presented to minimize the customer´s exposure to voltage sags. These measures cannot completely eliminate the impact of voltage sags on sensitive equipment, however. A case study is presented in this paper that includes measurement results that were used to characterize the voltage sags experienced on the utility system and in the industrial facility. Simulation results used to develop “area-of-vulnerability curves” for the industrial facility, mitigation equipment that was employed to improve the sensitive equipment´s ridethrough capability and the lessons learned from the systems approach analysis are presented
  • Keywords
    electrical faults; electricity supply industry; industrial power systems; power supply quality; power system protection; area-of-vulnerability curves; case study; electric utility; industrial customers; industrial facility; mitigation equipment; power system voltage sags; ridethrough capability; systems approach analysis; Control systems; Fires; Frequency; Industrial plants; Industrial power systems; Lightning; Power quality; Power system faults; Temperature control; Voltage fluctuations;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/28.673725
  • Filename
    673725