• DocumentCode
    1371284
  • Title

    Sensitivity requirements of reactive load division circuits in aircraft electric systems

  • Author

    Sherrard, S. Emile

  • Author_Institution
    Naval Research Laboratory, Washington, D. C.
  • Volume
    73
  • Issue
    5
  • fYear
    1954
  • Firstpage
    279
  • Lastpage
    288
  • Abstract
    Reactive load unbalance among paralleled generators is analyzed to relate the largest unbalance with the sensitivity of the reactive load division circuit employed in the regulators and with the regulation characteristics of the individual generator-exciter-regulator units. The maximum permissible sensitivity of the reactive load division circuit is found, from stability considerations, to be determined by the unsaturated synchronous reactance of the paralleled generators. The design of the reactive load division circuit is discussed from a system viewpoint.
  • Keywords
    Current transformers; Equalizers; Generators; Rectifiers; Regulators; Sensitivity; Voltage control;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Part II: Applications and Industry, Transactions of the
  • Publisher
    ieee
  • ISSN
    0097-2185
  • Type

    jour

  • DOI
    10.1109/TAI.1954.6371433
  • Filename
    6371433