Effect of Field-Voltage Source Impedance on Load-Rejection Test Results of Large-Rating Synchronous Generators
Author
De Oliveira, Sebastião E M ; De Souza, João Antunes
Author_Institution
Escola Politec., Brazil
Volume
26
Issue
1
fYear
2011
fDate
3/1/2011 12:00:00 AM
Firstpage
30
Lastpage
35
Abstract
This paper presents a technique to determine the effect of the field-voltage circuit during the load-rejection test of a large-rating salient-pole synchronous generator. Once the circuit powered by a six-pulse converter connected to the excitation transformer of the generator unit corresponds to a power-supply voltage not constant immediately after the load rejection, a careful evaluation of the resulting signals is necessary to extract rotor and stator parameters from the comparison with theoretical expressions derived under the assumption of constant-field terminal voltage and excluding external effects. The results obtained in the load-rejection test of a 179-MVA, 13.8-kV generating unit at Nova Ponte power plant show the parameters that are more affected by the external impedance in series with the rotor circuit and how to compensate them.
Keywords
power transformers; rotors; stators; synchronous generators; Nova Ponte power plant; apparent power 179 MVA; excitation transformer; field-voltage circuit; field-voltage source impedance; load rejection; pulse converter; rotor circuit; salient-pole synchronous generator; stator; voltage 13.8 kV; Direct-axis synchronous reactance; load-rejection tests; quadrature-axis synchronous reactance; synchronous machines;
fLanguage
English
Journal_Title
Energy Conversion, IEEE Transactions on
Publisher
ieee
ISSN
0885-8969
Type
jour
DOI
10.1109/TEC.2010.2066277
Filename
5623335
Link To Document