• DocumentCode
    1372249
  • Title

    Protection Planning and System Design to Reduce Arc-Flash Incident Energy in a Multi-Voltage-Level Distribution System to 8 \\hbox {cal}/\\hbox {cm}^{2} (HRC 2) or Less

  • Author

    Das, J.C.

  • Author_Institution
    AMEC E&C Services Inc., Tucker, GA, USA
  • Volume
    47
  • Issue
    1
  • fYear
    2011
  • Firstpage
    408
  • Lastpage
    420
  • Abstract
    This paper demonstrates that, in a multi-voltage-level (medium and low voltages) distribution system, the incident energy can be reduced to 8 cal/cm2 (hazard risk category 2) or even less, so that a personal protective equipment outfit of greater than two is not required. This is achieved with the current state-of-the-art equipment and protective devices. It is recognized that, in the existing distribution systems, not specifically designed with this objective, it may not be possible to reduce the arc-Flash hazard to this low level, unless major changes in the system design and protection are made. A typical industrial distribution system is analyzed, and tables and time-coordination plots are provided to support the analysis. Unit protection schemes and practical guidelines for arc-Flash reduction are provided. The methodology of IEEE 1584 is used for the analyses. Reducing HRC also reduces the fault damage to the equipment.
  • Keywords
    IEEE standards; arcs (electric); fault diagnosis; health hazards; power distribution planning; power distribution protection; protective clothing; HRC reduction; IEEE 1584; arc flash hazard; arc flash incident energy reduction; fault damage reduction; industrial distribution system; multivoltage level distribution system; personal protective equipment outfit; practical guidelines; protection planning; state-of-the-art equipment; state-of-the-art protective devices; system design; time-coordination plots; unit protection schemes; Arc discharges; Current limiters; Hazards; Protective relaying; Current-limiting fuses; differential relaying; hazard risk category (HRC) reduction; light-sensing protection; maintenance (arc-Flash reduction) switch; protective relay coordination;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.2010.2091378
  • Filename
    5624580