DocumentCode :
1374621
Title :
Calculating Steady-State Operating Conditions for Doubly-Fed Induction Generator Wind Turbines
Author :
Padrón, José Fernando Medina ; Lorenzo, Andrés Elías Feijóo
Author_Institution :
Dept. de Ing. Electr., Univ. de Las Palmas de Gran Canaria, Las Palmas de Gran Canaria, Spain
Volume :
25
Issue :
2
fYear :
2010
fDate :
5/1/2010 12:00:00 AM
Firstpage :
922
Lastpage :
928
Abstract :
In this paper an analysis of steady-state operation in doubly-fed induction generator (DFIG) wind turbines (WT) is presented. A method based on the Newton-Raphson (NR) algorithm is proposed for obtaining the steady-state electrical variables of the machine under certain given conditions. It is of interest in the load flow analysis, when these machines are present in electrical system, but also for gaining initial conditions for dynamic analysis, as the variables in dynamic models must coincide with those in stationary models during steady-state operation. Results obtained from the stationary analysis allow us to initialize electrical variables for use in a third-order dynamic model of the DFIG. The method presented in this paper does not make use of a d-q reference frame. Some approximations made in other works have not been assumed here, which allowed us to obtain more accurate results.
Keywords :
Newton-Raphson method; asynchronous generators; load flow; wind turbines; Newton-Raphson algorithm; doubly fed induction generator; dynamic analysis; load flow analysis; steady state electrical variable; steady state operating conditions; third order dynamic model; wind turbines; Doubly-fed induction generator; load flow analysis; wind energy;
fLanguage :
English
Journal_Title :
Power Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8950
Type :
jour
DOI :
10.1109/TPWRS.2009.2036853
Filename :
5371953
Link To Document :
بازگشت