• DocumentCode
    1375722
  • Title

    Dielectric admittances in current transformers

  • Author

    Arnold, A.H.M.

  • Volume
    97
  • Issue
    60
  • fYear
    1950
  • fDate
    12/1/1950 12:00:00 AM
  • Firstpage
    727
  • Lastpage
    732
  • Abstract
    The ratio of a current transformer having appreciable capacitance between windings is dependent upon whether and how the windings are connected together. There are five ratios which may be defined without a knowledge of the external circuits, one of them without any direct link between windings and four with a low-resistance link between one primary terminal and one secondary terminal; only two of these ratios may be measured directly by a simple bridge. Formulae are developed in the paper by means of which all the ratios may be deduced from simple bridge measurements; the adequacy of the formulae is tested by experimental measurements. A simple test is developed for determining quickly whether the effect of capacitance is appreciable in a transformer of unknown characteristics, and methods of construction of low-capacitance transformers are discussed.
  • Keywords
    capacitance;
  • fLanguage
    English
  • Journal_Title
    Proceedings of the IEE - Part II: Power Engineering
  • Publisher
    iet
  • Type

    jour

  • DOI
    10.1049/pi-2.1950.0204
  • Filename
    5239996