Title :
Optimal Design Specifications of 22.9 kV HTS-FCL Applied in Real Korean Power System
Author :
Yoon, Jae-Young ; Lee, Seung-Ryul ; Yang, B.
Author_Institution :
Korea Electrotechnol. Res. Inst. [KERI], Changwon, South Korea
Volume :
21
Issue :
3
fYear :
2011
fDate :
6/1/2011 12:00:00 AM
Firstpage :
2184
Lastpage :
2187
Abstract :
KEPCO decided to apply the HTS FCL and cable in real substation in 2009. This is the first commercial demonstration case and starting point of the HTS equipment in South Korea, even though this is not a general perfect commercialization. For a successful application on this commercialization preliminary, it is quite important to design the HTS-FCL specification with regard to the current status of the application site (for example, the existence of NGR (Neutral Grounding Reactor), 3-winding low% impedance and so on). This paper evaluates the necessary and sufficient design specifications of the 22.9 kV HTS-FCL to fulfill the real power system conditions. It investigates the detailed design criteria, short circuit capacity, FCL impedance, protection scheme, fault limiting type and other design parameters to learn the real status of ICHEON substation which will be using the HTS- FCL.
Keywords :
earthing; fault current limiters; high-temperature superconductors; power system protection; substations; FCL impedance; HTS-FCL; ICHEON substation; KEPCO; NGR; fault limiting type; high-temperature superconductors; neutral grounding reactor; optimal design specification; protection scheme; real Korean power system condition; short circuit capacity; voltage 22.9 kV; Circuit breakers; Circuit faults; Fault currents; High temperature superconductors; Impedance; Substations; Design specification; HTS-FCL; fault current; protection scheme;
fLanguage :
English
Journal_Title :
Applied Superconductivity, IEEE Transactions on
Publisher :
ieee
ISSN :
1051-8223
Type :
jour
DOI :
10.1109/TASC.2010.2086418
Filename :
5635363
Link To Document :
بازگشت