DocumentCode :
1378708
Title :
A new interruption method for low-voltage, small-capacity, air-break contactors
Author :
Mori, Teijiro ; Koyama, Kenichi ; Okado, Hiroyuki ; Masuda, Shigeru
Author_Institution :
Mitsubishi Electr. Corp., Hyogo, Japan
Volume :
27
Issue :
1
fYear :
1991
Firstpage :
161
Lastpage :
166
Abstract :
An interruption method for low-voltage, small-capacity, air-break contactors is developed. The features of the construction of this method are that a slit is formed in the stationary conductor with a contact, and an arc runner is located on the slit. The operation, construction, experimental conditions and results, and applications of the method are discussed. The method shortens the maximum arcing time in a 726 V, 74 A circuit by about 70% and reduces contact wear in a 440 V, 80 A circuit by 21%, compared with the conventional method. This method produces enough magnetic flux density to drive an arc. The shortening of the maximum arcing time and reduction of the contact wear are considered to be due to the electromagnetic drive of the arc. This method has been applied to contactors of 18 A and 21 A frames; it increased their rated operational current for AC3 duty at 660 V by 50%
Keywords :
contactors; 440 V; 726 V; 74 A; 80 A; AC3 duty; LV air-break contactors; arc runner; contact wear; electromagnetic drive; interruption method; magnetic flux density; maximum arcing time; rated operational current; Bridges; Conductors; Contactors; Costs; Electromagnetic analysis; Industry Applications Society; Magnetic fields; Solid state circuits; Switching circuits; Vacuum arcs;
fLanguage :
English
Journal_Title :
Industry Applications, IEEE Transactions on
Publisher :
ieee
ISSN :
0093-9994
Type :
jour
DOI :
10.1109/28.67548
Filename :
67548
Link To Document :
بازگشت