Abstract :
Compared with the Doubly fed induction generators (DFIG), the brushless doubly fed induction generator (BDFIG) has a commercial potential for wind power generation due to its lower cost and higher reliability. In the most recent grid codes, wind generators are required to be capable of riding through low voltage faults. As a result of the negative sequence, induction generators response differently in asymmetrical voltage dips compared with the symmetrical dip. This paper gave a full behavior analysis of the BDFIG under different types of the asymmetrical fault and proposed a novel control strategy for the BDFIG to ride through asymmetrical low voltage dips without any extra hardware such as crowbars. The proposed control strategies are experimentally verified by a 250-kW BDFIG.
Keywords :
asynchronous generators; brushless machines; machine control; power generation control; power generation faults; power generation reliability; wind power plants; wind turbines; BDFIG; asymmetrical fault; asymmetrical low-voltage ride through; asymmetrical voltage dips; brushless doubly fed induction generators; grid codes; power 250 kW; wind generators; wind power generation; wind turbines; AC generators; doubly fed induction generators (DFIG); fault ride-through; wind energy;
fLanguage :
English
Journal_Title :
Energy Conversion, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8969
Type :
jour
DOI :
10.1109/TEC.2013.2261818
Filename :
6544266
Link To Document :
بازگشت