• DocumentCode
    1382347
  • Title

    High-frequency transient voltage measuring techniques

  • Author

    Lord, H.W.

  • Author_Institution
    General Electric Company, Schenectady, N. Y.
  • Volume
    82
  • Issue
    5
  • fYear
    1963
  • Firstpage
    602
  • Lastpage
    605
  • Abstract
    Transient voltages continue to cause insulation failures of transformers in a variety of applications. There is evidence that some voltage transients may include frequency components up to 100 mc (megacycles) of substantial peak-to-peak amplitude. Conventional techniques for securing reasonably accurate oscillographic recordings of high-frequency transients were found to be inadequate. Systems were devised which couple the oscillograph to the point of voltage measurement by 50-ohm cables. Through the combination of special signal-cable filters and relatively simple shielding techniques, the effects of spurious signals upon the oscillographic recording of high-frequency transient voltages can be virtually eliminated.
  • Keywords
    Cable shielding; Capacitors; Coaxial cables; Oscilloscopes; Power cables; Transient analysis; Voltage measurement;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Part I: Communication and Electronics, Transactions of the
  • Publisher
    ieee
  • ISSN
    0097-2452
  • Type

    jour

  • DOI
    10.1109/TCE.1963.6373271
  • Filename
    6373271