• DocumentCode
    1383030
  • Title

    Recovery characteristics of vacuum arcs

  • Author

    Cobine, J. D. ; Farrall, G. A.

  • Author_Institution
    General Electric Company, Schenectady, N. Y.
  • Volume
    82
  • Issue
    2
  • fYear
    1963
  • fDate
    5/1/1963 12:00:00 AM
  • Firstpage
    246
  • Lastpage
    253
  • Abstract
    A study has been made of the breakdown and recovery strength characteristics of experimental vacuum interrupters incorporating a variety of contact materials. Our data show that much of the breakdown strength for these devices is gained in less than a 1/8-inch gap length. Experiments using a synthetic test system indicate that these experimental switches recover nearly all of their breakdown strength in 1 to 15 ¿sec (microseconds) after the cessation of peak arc current ranging from 400 to 3,200 amp (amperes).
  • Keywords
    Cathodes; Metals; Switches; Vacuum arcs;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Part I: Communication and Electronics, Transactions of the
  • Publisher
    ieee
  • ISSN
    0097-2452
  • Type

    jour

  • DOI
    10.1109/TCE.1963.6373383
  • Filename
    6373383