Title :
Recovery characteristics of vacuum arcs
Author :
Cobine, J. D. ; Farrall, G. A.
Author_Institution :
General Electric Company, Schenectady, N. Y.
fDate :
5/1/1963 12:00:00 AM
Abstract :
A study has been made of the breakdown and recovery strength characteristics of experimental vacuum interrupters incorporating a variety of contact materials. Our data show that much of the breakdown strength for these devices is gained in less than a 1/8-inch gap length. Experiments using a synthetic test system indicate that these experimental switches recover nearly all of their breakdown strength in 1 to 15 ¿sec (microseconds) after the cessation of peak arc current ranging from 400 to 3,200 amp (amperes).
Keywords :
Cathodes; Metals; Switches; Vacuum arcs;
Journal_Title :
American Institute of Electrical Engineers, Part I: Communication and Electronics, Transactions of the
DOI :
10.1109/TCE.1963.6373383