• DocumentCode
    1384769
  • Title

    Arc root mobility during contact opening at high current

  • Author

    McBride, John W. ; Weaver, P.M. ; Jeffery, P.A.

  • Author_Institution
    Dept. of Mech. & Electr. Eng., Southampton Univ., UK
  • Volume
    21
  • Issue
    1
  • fYear
    1998
  • fDate
    3/1/1998 12:00:00 AM
  • Firstpage
    61
  • Lastpage
    67
  • Abstract
    This paper presents a test system, designed for the investigation of short circuit arcs related to miniature circuit breakers operating in a 240 V, AC supply. An optical fiber imaging system is used to identify arc root motion, with short circuit current up to 6 kA. Two methods are used to measure contact motion, a noncontact linear position sensor, and the optical fiber array. The optical fiber array uses software image processing to identify the position of the arc roots in the arc chamber. The identification of the arc roots allows for a study of the arc immobility at the initial stages of the event. Results are presented on variation of peak current level and arc runner materials on arc root motion for one geometry. The cathode root motion is shown to dominate the event
  • Keywords
    circuit breakers; circuit-breaking arcs; optical fibres; optical images; 240 V; 6 kA; arc immobility; arc root mobility; arc runner materials; cathode root motion; circuit breakers; contact opening; noncontact linear position sensor; optical fiber imaging system; peak current level; short circuit arcs; software image processing; test system; Circuit breakers; Circuit testing; Motion measurement; Optical arrays; Optical fibers; Optical imaging; Position measurement; Sensor arrays; Short circuit currents; System testing;
  • fLanguage
    English
  • Journal_Title
    Components, Packaging, and Manufacturing Technology, Part A, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9886
  • Type

    jour

  • DOI
    10.1109/95.679034
  • Filename
    679034