Title :
Positional protection of transmission line using fault generated high frequency transient signals
Author :
Bo, Z.Q. ; Redfern, M.A. ; Weller, G.C.
Author_Institution :
ALSTOM Protection & Control Ltd., UK
fDate :
7/1/2000 12:00:00 AM
Abstract :
This paper presents a new technique for high-speed protection of transmission lines, the positional protection technique. The technique uses a fault transient detector unit at the relaying point to capture fault generated high frequency transient signals contained in the primary currents. The decision to trip is based on the relative arrival times of these high frequency components as they propagate through the system. Extensive simulation studies of technique were carried out to examine the response to different power system and fault conditions. Results show that the scheme is insensitive to fault type, fault resistance, fault inception angle and system source configuration, and that it is able to offer both very high accuracy and speed in fault detection
Keywords :
electric current measurement; fault location; power system faults; power system transients; power transmission lines; power transmission protection; fault conditions; fault generated high frequency transient signals; fault transient detector unit; high-speed protection; positional protection; power system conditions; relative arrival times; relaying point; transmission line protection; Detectors; Fault detection; Frequency; Power system simulation; Power system transients; Power transmission lines; Protection; Protective relaying; Signal generators; Transmission lines;
Journal_Title :
Power Delivery, IEEE Transactions on