• DocumentCode
    1387599
  • Title

    Positional protection of transmission line using fault generated high frequency transient signals

  • Author

    Bo, Z.Q. ; Redfern, M.A. ; Weller, G.C.

  • Author_Institution
    ALSTOM Protection & Control Ltd., UK
  • Volume
    15
  • Issue
    3
  • fYear
    2000
  • fDate
    7/1/2000 12:00:00 AM
  • Firstpage
    888
  • Lastpage
    894
  • Abstract
    This paper presents a new technique for high-speed protection of transmission lines, the positional protection technique. The technique uses a fault transient detector unit at the relaying point to capture fault generated high frequency transient signals contained in the primary currents. The decision to trip is based on the relative arrival times of these high frequency components as they propagate through the system. Extensive simulation studies of technique were carried out to examine the response to different power system and fault conditions. Results show that the scheme is insensitive to fault type, fault resistance, fault inception angle and system source configuration, and that it is able to offer both very high accuracy and speed in fault detection
  • Keywords
    electric current measurement; fault location; power system faults; power system transients; power transmission lines; power transmission protection; fault conditions; fault generated high frequency transient signals; fault transient detector unit; high-speed protection; positional protection; power system conditions; relative arrival times; relaying point; transmission line protection; Detectors; Fault detection; Frequency; Power system simulation; Power system transients; Power transmission lines; Protection; Protective relaying; Signal generators; Transmission lines;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.871348
  • Filename
    871348