• DocumentCode
    1387666
  • Title

    Electrical design parameters of all-dielectric-self-supporting fiber optic cable

  • Author

    Tuominen, Monty W. ; Olsen, Robert G.

  • Author_Institution
    USDOE, Portland, OR, USA
  • Volume
    15
  • Issue
    3
  • fYear
    2000
  • fDate
    7/1/2000 12:00:00 AM
  • Firstpage
    940
  • Lastpage
    947
  • Abstract
    A lumped circuit model for calculating voltages and currents on all-dielectric self-supporting (ADSS) fiber optic cable near high voltage transmission lines has been developed. The model has been used to show that contamination levels, tower attachment points, relative ADSS and conductor sag and electrical phasing of the conductors are important parameters and must be considered in calculations, especially when determining the possibility of dry band arcs which could lead to cable damage
  • Keywords
    arcs (electric); optical cables; overhead line mechanical characteristics; poles and towers; power overhead lines; telecommunication transmission lines; all-dielectric-self-supporting fiber optic cable; cable damage; conductor sag; contamination levels; current calculation; dry band arcs; electrical design parameters; electrical phasing; high voltage transmission lines; lumped circuit model; tower attachment points; voltage calculation; Arc discharges; Conductors; Contamination; Corona; Optical design; Optical fiber cables; Optical fibers; Poles and towers; Power cables; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.871356
  • Filename
    871356