DocumentCode :
1389000
Title :
Development of high-voltage air-break circuit-breakers with insulated-steel-plate arc chutes
Author :
Fay, F.S. ; Thomas, J.A. ; Legg, D. ; Morton, J.S.
Volume :
106
Issue :
29
fYear :
1959
fDate :
10/1/1959 12:00:00 AM
Firstpage :
381
Lastpage :
391
Abstract :
The paper reports research and development done over the past ten years to investigate the principles of operation of a.c. air-break circuit-breakers for voltages up to 15kV and breaking capacities up to 500 MVA. Much of the research data on contacts, arc runners, the behaviour and control of arcs in arc chutes and arc extinction is of a fundamental nature and suitable for general application. High-speed photography played an important part in obtaining the data. The arc chute that was finally developed is of the insulated-steel-plate type, but no blow-out coil is used. The research has been applied to the design and manufacture of air-break circuit-breakers with British ratings up to 250 MVA at 3.3 kV, and up to 500 MVA at 6.6kV, 11 kV and 15kV, and American ratings up to 750 MVA. Details of the performance of the circuit-breakers and the effect of the system characteristics are given. Development is continuing to higher voltages and ratings.
Keywords :
circuit breakers; power transmission; switching circuits;
fLanguage :
English
Journal_Title :
Proceedings of the IEE - Part A: Power Engineering
Publisher :
iet
ISSN :
0369-8882
Type :
jour
DOI :
10.1049/pi-a.1959.0108
Filename :
5242504
Link To Document :
بازگشت