DocumentCode :
1389027
Title :
Application of Equal Area Criterion Conditions in the Time Domain for Out-of-Step Protection
Author :
Paudyal, Sumit ; Ramakrishna, Gokaraju ; Sachdev, Mohindar S.
Author_Institution :
Dept. of Electr. & Comput. Eng., Univ. of Waterloo, Waterloo, ON, Canada
Volume :
25
Issue :
2
fYear :
2010
fDate :
4/1/2010 12:00:00 AM
Firstpage :
600
Lastpage :
609
Abstract :
A new procedure for out-of-step protection by mapping the equal area criterion conditions to the time domain is proposed in this paper. The classification between stable and out-of-step swings is done using the accelerating and decelerating energies, which represents the area under the power-time curve. The proposed methodology is simple and overcomes some of the difficulties associated with the previous techniques. The proposed approach is based only on the local electrical quantities available at the relay location, and does not depend on the network configuration and parameters. The proposed algorithm has been tested on a single-machine infinite bus and a three-machine infinite bus system using software simulations. A digital prototype of the relay has also been implemented on the hardware and its performance has been assessed in a closed-loop mode using a real-time digital simulator. The simulation results and the hardware testing results confirm the validity of the approach presented.
Keywords :
relay protection; time-domain analysis; a real-time digital simulator; closed-loop mode; equal area criterion conditions; hardware testing; local electrical quantities; out-of-step protection; power-time curve; relay location; single-machine infinite bus; software simulations; three-machine infinite bus system; time domain; Equal area criterion; out-of-step; power swings; relays;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2009.2032326
Filename :
5393038
Link To Document :
بازگشت