Characterizing the breakdown behavior of rodplane air gap under impulse over-voltage
Author :
Nourirad, Ghasem ; Izadi, Maziar ; Gomes, Chandima ; Kadir, M. Z. A. Ab
Author_Institution :
Electr. & Electron. Eng. Dept., Univ. Putra Malaysia, Serdang, Malaysia
fYear :
2014
fDate :
24-25 March 2014
Firstpage :
450
Lastpage :
454
Abstract :
Experimental test has been done due to realize the characteristics of the behavior of voltage-time in the case of rod-plane air gap of 70mm and 100mm. Impulse voltage has been applied in this regard to find out the voltage at breakdown level, time to breakdown value, time to complete discharge, comparison of trajectory of the waveshape and the significant points of the increasing the gap distance. The results depicted that, the breakdown voltage was dependent on the integral of applied voltage and discharge time was more dependent on the gap value compared to other conditions.
Keywords :
air gaps; electric breakdown; applied voltage; breakdown behavior; breakdown voltage; discharge time; gap value; impulse overvoltage; rod plane air gap; Breakdown voltage; Conferences; Discharges (electric); Humidity; Lightning; Poles and towers;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering and Optimization Conference (PEOCO), 2014 IEEE 8th International
Conference_Location :
Langkawi
Print_ISBN :
978-1-4799-2421-9
Type :
conf
DOI :
10.1109/PEOCO.2014.6814471
Filename :
6814471