DocumentCode :
1389848
Title :
Measurement of discharges in generator stator insulation
Author :
Douglas, J.L.
Volume :
109
Issue :
3
fYear :
1962
fDate :
5/15/1905 12:00:00 AM
Firstpage :
56
Lastpage :
61
Abstract :
Investigations of a number of generator stator-insulation failures have shown that breakdowns of several machines generating at 33 kV were initiated by discharge erosion of the insulation. The paper describes a method of measuring discharges in stator insulation. The technique consists in counting the number of discharge pulses exceeding a certain level. It is concluded that this proposed instrument has several advantages over other types of discharge detector. It is shown that, at the present time, this method, or indeed any other means of measuring discharges, cannot determine the depth of discharge erosion in generator stator insulation. In a complete stator winding, the internal discharges tend to be concealed by slot discharges, which may or may not be harmful, depending on the surface conductivity of the dielectric.
Keywords :
electric generators; electronics applications; machine insulation;
fLanguage :
English
Journal_Title :
Proceedings of the IEE - Part A: Power Engineering
Publisher :
iet
ISSN :
0369-8882
Type :
jour
DOI :
10.1049/pi-a.1962.0011
Filename :
5242665
Link To Document :
بازگشت