DocumentCode :
1390542
Title :
The mathematical basis of the absolute calibration of voltage dividers for the measurement of front-chopped impulse waves
Author :
Ouyang, M.
Volume :
108
Issue :
40
fYear :
1961
fDate :
8/1/1961 12:00:00 AM
Firstpage :
327
Lastpage :
330
Abstract :
A new technique has recently been developed in the absolute calibration of dividers for the measurement of an impulse voltage which is chopped at its front within a fraction of a microsecond. By this technique the theoretical error of a divider under idealized conditions can be calculated from the `ultimate time-displacement¿, which is derived from the response of the divider to a unit-function voltage. The paper discusses theoretically the basis and limitations of this technique and derives some properties of the ultimate time-displacement which are of practical significance.
Keywords :
voltage dividers; voltage measurement;
fLanguage :
English
Journal_Title :
Proceedings of the IEE - Part A: Power Engineering
Publisher :
iet
ISSN :
0369-8882
Type :
jour
DOI :
10.1049/pi-a.1961.0068
Filename :
5242796
Link To Document :
بازگشت