DocumentCode :
1390714
Title :
Transmission of voltage signals through serially connected relay contacts
Author :
Bizjak, Martin
Author_Institution :
Dept. of Electroenergetic Syst., Univ. Edvard Kardelj Ljubljana, Yugoslavia
Volume :
14
Issue :
2
fYear :
1991
fDate :
6/1/1991 12:00:00 AM
Firstpage :
337
Lastpage :
341
Abstract :
When more than one switching contact in series transmits electric signals, the high-resistance tail of the contact resistance distribution function has an influence on the voltage fall statistics of the contact series. Due to this effect, the reduction of voltage-fall on the receiver can result in reduced reliability of its operation. When the behavior of contact series is concerned, some characteristics of contact contamination can be distinguished from statistical treatment of transmitted voltage, measured on the load resistor. Voltage fall statistics of a multicontact system, when assuming Weibull distribution function of contact resistance for individual contact, were derived from basic probability analysis for nominally clean contacts. It can be helpful in the research of contaminated contacts with non-Weibull statistics in order to recognize some contact surface phenomena
Keywords :
contact resistance; electrical contacts; relays; statistical analysis; Weibull distribution function; contact resistance distribution function; high-resistance tail; load resistor; multicontact system; reliability; serially connected relay contacts; switching contact; voltage fall statistics; voltage signals; Contact resistance; Contamination; Distribution functions; Electrical resistance measurement; Pollution measurement; Probability distribution; Relays; Resistors; Statistical distributions; Voltage measurement;
fLanguage :
English
Journal_Title :
Components, Hybrids, and Manufacturing Technology, IEEE Transactions on
Publisher :
ieee
ISSN :
0148-6411
Type :
jour
DOI :
10.1109/33.87314
Filename :
87314
Link To Document :
بازگشت