DocumentCode :
1391159
Title :
Influence of test methods on dc flashover performance of ice-covered composite insulators and statistical analysis
Author :
Xingliang Jiang ; Maoqiang Bi ; Jianlin Hu ; Zhijing Zhang ; Yunfeng Xia
Author_Institution :
State Key Lab. of Power Transm. Equip. & Syst. Security & New Technol., Chongqing Univ., Chongqing, China
Volume :
19
Issue :
6
fYear :
2012
fDate :
12/1/2012 12:00:00 AM
Firstpage :
2019
Lastpage :
2028
Abstract :
Operational statistics and studies have revealed that, the reduction of insulation strength of transmission line insulators caused by icing is one of the critical reasons of the power grid faults. This paper compares of various test methods for evaluating the flashover characteristic of ice-covered composite insulators. Two types of composite insulators, i.e. FXBW-±800/530 short sample and FXBW-110/100 are investigated. The influences of various test methods on flashover performance of ice-covered insulators are studied in an artificial climate chamber. The test results revealed the influences are significant. The average flashover voltage (Uav) using even raising method is highest, followed by the 50% withstand voltage (U50%) which is corresponding to up and down method, the lowest flashover voltage (Uf.min) using Ucurve method is the third, and the maximum withstand voltage (Uws) using the maximum withstand voltage method is the lowest. Through the statistical analysis, the U50% can be estimated by Uav and σav though the estimated value Ue (Ue=(Uav-k1σav)/( 1+k2δe)). The estimated errors (Ee) are less than 1.80% in this paper. Therefore, there is an intrinsic relationship among the test results obtained by using various test methods. This simplifies selection of the appropriate test method according to the testing specific circumstances.
Keywords :
composite insulators; flashover; insulator testing; power transmission lines; statistical analysis; DC flashover performance; FXBW-110-100; FXBW-800-530; Ucurve method; artificial climate chamber; flashover characteristic; flashover voltage; ice-covered composite insulators; insulation strength; maximum withstand voltage method; operational statistics; power grid faults; raising method; statistical analysis; transmission line insulators; up-down method; Equations; Flashover; Ice; Insulators; Mathematical model; Meteorology; Statistical analysis; composite insulator; conductivity of icing water; dc; flashover performance; icing; statistical analysis; test method;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2012.6396961
Filename :
6396961
Link To Document :
بازگشت