  • Abstract
    This paper proposes a new control method to reduce overvoltages due to three-phase reclosing for shunt compensated transmission lines (TL). The method detects the first minimum voltage region of the beating across the circuit breakers after protection dead time and works independently of voltage zero crossing, reducing significantly the reclosure time. The controller was tested on a Real Time Digital Simulator (RTDS) and its performance was compared to the traditional preinsertion resistor approach and another existing control method.
  • Keywords
    circuit breakers; overvoltage; performance evaluation; power transmission control; power transmission lines; reactors (electric); circuit breakers; performance evaluation; preinsertion resistor; real time digital simulator; shunt reactor-compensated transmission lines; three-phase reclosing method; voltage zero crossing; Controlled switching; electromagnetic transients; switching overvoltages; three-phase reclosing; transmission lines;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2010.2084111
  • Filename
    5654622